Instruction for Test Unit for Stroco Oil Heater 35.00 M

Working description:

Starting.

The first 3 seconds the steering carry out an internal calibration. No activity is seen in the display or the light-emitting diodes, no contacts are active.

If the internal calibration is okay the steering goes in test mode - else a failure is reported.

 

Test mode.

Water pump, blower, room blower, ignition/pre-heater and magnet valve can be activated and the power consumption for these can be read in display.

The boiler temperature and a figure for the luminous intensity on the photo sensor can also be read.

 

Mode of operation for buttons.

The test-unit shows total power consumption. A continued pressure on photo or temp. activates light in concerned button and a figure for the luminous intensity or the temperature can be read in the display. If water pump, blower, room blower, ignition/pre-heating or magnet valve are activated, these will stay active, but the light-emitting diode in the button is turned off as long as photo or temp. is pressed in.

 

Test/auto

Changes between normal and test mode.

 

Photo and temp.

A continued pressure on the button activates the function.

 

Auto mode.

The test-unit works as a standard HP35.00 steering. Total power consumption, temperature and luminous intensity on photo sensor can also be read. When auto mode is selected the steering always carry out a new start.

 

Active buttons.

Test, auto, photo and temp.

 

Active light-emitting diodes () only if selected.

Auto, (photo), (temp.)

Mode of operation for buttons.

The test-unit shows total power consumption. A pressure on photo or temp. activates light in concerned button and a figure for the luminous intensity or the temperature is read in display.